HVAC Fault Code Lookup

Type the code your furnace, air handler, heat pump or wall control is showing. You get what it means, what usually causes it and what to check first, for 388 codes across nine control board families.

Check error codes by brand

Brands that share a control board are grouped, so a Bryant owner reads the Carrier list and a Tempstar owner reads the ICP list.

Codes that point to the blower motor

A code names the safety that tripped, not the part that failed. These are the codes where the indoor blower motor is the direct suspect, and the airflow codes where it is one of the usual causes.

Blower motor faults

Airflow faults: check these first

  • Goodman 4 flashesOpen high limit
  • Carrier 58-series 13Limit or flame rollout switch lockout
  • Carrier 58-series 33Limit or flame rollout switch is open
  • Trane 4 blinksTemperature switch problem / over temperature limit
  • Lennox 250Primary limit switch open
  • Lennox 252Discharge air temperature high
  • Lennox 274Limit switch open more than three minutes
  • Lennox 311Heat firing rate reduced to match available airflow (cutback mode)
  • Carrier Infinity 13Limit switch lockout
  • Carrier Infinity 33Limit fault / lost inverter communications
  • Carrier Infinity 161Excess static pressure stage down
  • Carrier Infinity 194Possible frozen coil
  • Carrier Infinity 210Excessive static pressure encountered
  • ICP (Arcoaire) 4 flashesHigh limit switch open
  • Ducane 4 flashesHigh limit switch open

A dirty filter, blower wheel or coil and high static pressure cause most of these. If the motor is the fault, match it by model number.

Goodman, Amana & Daikin LED flash codes

Goodman, Amana and Daikin gas furnaces report faults on a red LED on the control board, behind the blower compartment door. Count the flashes between pauses: the count is the code. A light that stays on, stays off or flashes without a pause is a code of its own. Four flashes is an open high limit, which is an airflow fault in most cases. 20 codes on 14 flash counts.

CodeWhat it meansCheck firstLevel
1 flashIgnition failure - retries exceeded / flame failureThe furnace tried to light and could not prove flame, so it has locked out.Amana boards: Flame failure / lockout from excessive ignition retriesClean the flame sensor with fine steel wool.Critical
2 flashesPressure switch stuck closedThe pressure switch is closed when the inducer is off, so the control will not start a cycle.Amana boards: Draft inducer not operating, or pressure switch circuit closedDisconnect the hose and confirm the switch opens.Critical
3 flashesPressure switch stuck openThe pressure switch will not close when the inducer runs.Amana boards: Open pressure switchCheck the hose for blockage, water and correct routing.Critical
4 flashesOpen high limitThe high limit switch has opened, which is nearly always an airflow problem.Amana boards: Pressure error / high limit errorAirflowReplace the filter and open all registers.Critical
5 flashesFlame sensed with gas valve offThe control sees flame when there is no call for heat and the valve should be closed.Amana boards: Flame sensed without a call for heatShut the gas off and see whether the code clears.Critical
6 flashesOpen rollout switchThe flame rollout switch has tripped, meaning flame or hot gas escaped the burner compartment. Serious safety trip.Find and correct the cause before resetting.Critical
7 flashesLow flame senseThe flame signal is weak. The furnace runs but will start dropping out.Amana boards: Faulty flame sensorClean the flame sensor and check microamps.Warning
8 flashesIgniter errorThe igniter circuit is faulty, so the furnace cannot light.Measure igniter resistance and check the connector is seated.Critical
9 flashesOpen pressure switch with induced draft blower onThe pressure switch is open while the inducer is running.Inspect the hose for cracks, water and correct routing.Critical
Constant flashingReversed polarityLine and neutral are reversed at the furnace.Correct the line and neutral wiring and re-test.Critical
Constant red lightNo signal from thermostatThe control has power but no heat call.Check thermostat settings and wiring.Info
Continuous flashingReversed polarityLine and neutral are reversed at the furnace. The control needs correct polarity for flame sensing.Correct the line and neutral wiring.Critical
Light offControl failureNo light at all means the control has no power or has failed.Check the breaker, furnace switch and door switch.Critical
Light onNo signal from thermostatThe control has power but is not receiving a call from the thermostat.Confirm the thermostat is set to heat and calling.Info

Carrier, Bryant & Payne 58-series LED status codes

Non-communicating Carrier, Bryant and Payne gas furnaces flash a two-digit status code on the control board LED: short flashes are the first digit and long flashes the second, so three short and three long is 33. The board keeps the last code until power is cut or 48 hours after the fault clears. 14 codes.

Every code with its fix, step by step: Carrier furnace and AC error codes explained

CodeWhat it meansCheck firstLevel
11No previous codeThe control has no stored fault. Stored codes are cleared when power is interrupted, or 48 hours after a fault clears.Nothing to diagnose - this is the normal 'all clear' code.Info
12Blower on after power upPower was restored while a heat call was active, so the blower ran for 90 seconds.No action needed unless power is dropping out repeatedly.Info
13Limit or flame rollout switch lockoutThe furnace has locked out after repeated limit or rollout trips. It auto-resets after about three hours; a tripped rollout switch must be reset by hand.AirflowReplace the filter and check for closed dampers.Critical
14Ignition lockoutFour failed ignition attempts have locked the furnace out. It auto-resets after about three hours. See code 34 for the underlying cause.Work through the code 34 checks - this code is just the lockout that follows them.Critical
21Gas heating lockoutThe control has locked gas heating out and will not reset itself - power must be cycled.Check gas valve wiring; if correct, replace the control board.Critical
22Abnormal flame-proving signalFlame was detected while the gas valve was de-energised. The inducer keeps running until this clears.Shut off the gas and see if the code clears. Replace a passing valve - do not leave it in service.Warning
23Pressure switch did not openThe pressure switch was already closed with the inducer off.Check the hoses for blockage and confirm the switch opens with the inducer off.Warning
24Secondary voltage fuse is openThe 24VAC fuse has blown due to a short in the low-voltage wiring.Disconnect the thermostat wiring, replace the fuse, and reconnect circuits one at a time to find the short.Critical
31High-heat pressure switch or relay did not close or reopenedThe high-heat pressure switch never closed, or opened during high fire.Work through the code 32 checks as well - the causes overlap.Warning
32Low-heat pressure, draft safeguard or aux limit switch did not close or reopenedThe low-heat pressure switch, draft safeguard or auxiliary limit did not close. If it stays open five minutes, the inducer shuts off for 15 minutes before retrying.Inspect the vent for blockage, correct length and proper termination.Warning
33Limit or flame rollout switch is openThe high limit or flame rollout switch is currently open. If it stays open more than three minutes the code becomes a 13 lockout. Rollout switches need a manual reset.AirflowReplace the filter and check duct restrictions.Warning
34Ignition proving failureFlame was not proved, or was lost after the trial for ignition. The control retries three more times before locking out with code 14.Clean the flame sensor with fine steel wool.Warning
43Low-heat pressure, draft safeguard or auxiliary limit switch open while high-heat pressure switch is closedAn impossible switch combination - the low-heat side is open while the high-heat side is closed.Verify each hose is on the correct switch port, then work through codes 32 and 33.Warning
45Replace controlThe control board has detected an internal failure and needs to be replaced.Cycle power once to confirm, then replace the control board.Critical

Trane & American Standard LED blink codes

Trane and American Standard gas furnaces blink a red LED on the control board. Count the blinks: two is a flame failure lockout, three a pressure switch problem and four an over-temperature limit, which traces back to airflow in almost every case. A light that stays on, stays off or blinks without a pause is read differently from a counted code. 12 codes.

CodeWhat it meansCheck firstLevel
2 blinksFlame failure - retries exceededThe furnace lost or never established flame after its retries, so it has locked out. Often reported as the furnace blowing cold air.Clean the flame sensor and check microamps.Critical
3 blinksPressure switch problemThe pressure switch is not in the state the control expects.Check the vent and condensate drain.Critical
4 blinksTemperature switch problem / over temperature limitThe limit switch has opened - an airflow problem in almost every case.AirflowReplace the filter and open all registers.Critical
5 blinksFlame sensed when no flame should be presentThe control detects flame outside the normal sequence.Shut off the gas and see whether the code clears.Critical
6 blinks115VAC reversed polarity or poor groundingLine voltage polarity is reversed, or the furnace has a poor ground. Flame sensing depends on both being correct.Correct the line and neutral wiring.Critical
7 blinksGas valve circuit errorThere is a fault in the gas valve circuit.Check for 24VAC at the valve during a heat call and measure the coil resistance.Critical
8 blinksLow flame sense signalThe flame signal is weak.Clean the flame sensor and check microamps.Warning
9 blinksCheck igniterThe control has flagged the igniter circuit.Measure igniter resistance and check the connector.Critical
Constant fast blinkingNormal operationThe furnace is functioning normally.Nothing to do.Info
Constant slow blinkingNormal operationThe furnace is functioning normally.Nothing to do.Info
Red light constant offCheck powerNo power reaching the control.Check the breaker, furnace switch, door switch and control fuse.Critical
Red light constant onControl failureThe control board has failed.Replace the control board.Critical

Rheem & Ruud seven-segment codes (R96V and modulating)

Rheem and Ruud modulating furnaces such as the R96V show a two-character code on a seven-segment display on the control board. A one-hour soft lockout shows 10 alternating with the code that caused it. Codes 60 and 61 are blower faults (61 means the motor cannot run), and d6 flags a horsepower conflict between the motor and the model data. 19 codes.

CodeWhat it meansCheck firstLevel
One-hour lockout (soft lockout)The control has locked gas heating out for one hour. It is always shown alternating with a second code that tells you why - look for the other code on the display.Read the code alternating with 10 - that is the real fault.Critical
Failed ignitionThe furnace failed to light on this attempt. Up to three failures is not critical; after four consecutive failures the control enters a one-hour lockout and shows 11 alternating with 10.Check gas supply and inlet pressure.Warning
Low flame senseThe flame signal is weaker than it should be. The furnace still runs but will start dropping out if this is left alone.Clean the flame sensor with fine steel wool.Warning
Flame lost after establishedFlame was proved and then went out during the heating cycle. After five losses in a row the control enters a one-hour lockout showing 13 alternating with 10.Clean the sensor and re-check microamps while running.Warning
Flame present with gas valve off (unexpected flame)The control sees flame when the gas valve should be closed. This causes a one-hour lockout showing 14 alternating with 10.Shut off the gas and see whether the code clears - if it does, the valve is passing gas.Critical
Open fuseThe low-voltage fuse on the furnace control has opened, so there is no 24V control power.Disconnect the thermostat wiring and fit a new fuse. If it holds, the short is external.Critical
Over-temperature switch (rollout) openA rollout or over-temperature switch has opened, meaning hot gas or flame escaped the burner area. This is a serious safety trip.Find and correct the cause before resetting anything.Critical
Low pressure switch closed, inducer offThe low pressure switch is closed with the inducer off. The control tests for this before every cycle because a closed switch here means the safety is not working.Disconnect the hose and confirm the switch opens.Critical
Low pressure switch open, inducer on high speedThe low pressure switch will not close with the inducer running at high speed.Check the vent system for blockage and correct termination.Critical
Low pressure switch open, inducer on low speedThe low pressure switch will not close with the inducer at low speed. Often the furnace will still run on high fire.Check the vent and hoses first.Critical
High pressure switch closed, inducer offThe high pressure switch is closed with the inducer off, which should never happen.Replace the high pressure switch if it does not open with the hose off.Critical
High pressure switch open, inducer on high speedThe high pressure switch is open with the inducer at high speed. If the low pressure switch stays closed, the furnace drops to low fire and keeps running.Check the vent for blockage and correct termination.Critical
Water circuit openThe control cannot detect continuity between pins 1 and 2 of connector P4, which it uses to confirm both water sensors are present. Gas heating is blocked.Repair or replace the sensor wiring.Critical
Water sensedThe control has detected water in the collector box for at least ten seconds. Gas heating is stopped; cooling still works.Clear the condensate drain and trap.Critical
Blower fault - blower can still runThe blower has hit a limit set by the manufacturer but can keep running. Everything still operates, though airflow is compromised.Blower motorMeasure total external static pressure - it is almost always too high.Warning
Blower fault - motor cannot runThe blower motor has failed critically or tripped a limit that stops it running altogether. The furnace will not operate in any mode. This is the primary Rheem blower motor failure code.Blower motorKill power and spin the blower wheel by hand - check for drag, bearing noise or a loose wheel.Critical
No model dataThe furnace has no model data, so it does not know the blower speed and torque curve it needs. Nothing will run - not even a thermostat call.Fit the correct memory card into connector P6 on the furnace control.Critical
No valid model data on memory cardThe memory card is blank, corrupt or missing, but a good copy of the model data is still stored in the furnace control. The furnace should still run normally.Fit the correct original or replacement memory card.Warning
Horsepower conflict on memory cardThe horsepower the blower motor reports does not match the horsepower stored on the memory card, although the control's own copy does match the motor. The furnace should still operate.Blower motorRead the horsepower on the motor nameplate and compare with the furnace rating plate.Warning

Replacement blower motors:Rheem blower motorsRuud blower motors

Lennox iComfort & Comfort Sync alert codes

Lennox communicating systems show a numbered alert on the iComfort or Comfort Sync thermostat, together with the unit that raised it. The 200 range comes from the furnace or air handler, including 201 (lost communication with the indoor blower motor), 202 (motor size mismatch) and 292 (blower will not start); the 400 range covers the outdoor unit and compressor. Armstrong Air, AirEase, Concord and Ducane communicating equipment uses the same list. 143 codes.

CodeWhat it meansCheck firstLevel
201Lost communication with the indoor blower motorThe control can no longer talk to the variable-speed indoor blower motor. This is the classic Lennox blower motor communication alert.Blower motorConfirm line voltage at the motor's power connector.Critical
202Unit size code and blower motor size do not matchThe configured unit size does not agree with the horsepower the blower motor is reporting. The control will not run until they match.Blower motorRead the horsepower off the motor nameplate and compare with the furnace or air handler rating plate.Critical
203Unit size code has not been selectedNo unit size code has been configured, so the control does not know what blower speeds to use.Blower motorEnter the correct unit size code from the installation instructions.Critical
291Heating airflow below the minimum required levelThe furnace cannot move enough air to fire safely, so heating is blocked.Blower motorReplace the filter and open all registers and dampers.Critical
292Indoor blower motor will not startThe control commanded the blower to run and it did not. On a Lennox variable-speed system this is a direct blower motor fault.Blower motorKill power and spin the blower wheel by hand - it must turn freely with no bearing noise or drag.Critical
295Indoor blower motor overheatingThe blower motor is running hotter than it should. Left alone this will shorten its life and eventually cause a thermal trip.Blower motorMeasure total external static pressure - high static is the usual cause.Warning
312Blower cannot provide requested CFM due to high static pressureThe blower is at its limit and still cannot deliver the airflow the system wants.Blower motorMeasure total external static pressure and compare with the blower performance table.Warning
250Primary limit switch openThe main high limit switch has opened, which almost always means airflow across the heat exchanger is too low.AirflowReplace the filter and open all registers.Warning
252Discharge air temperature highSupply air is hotter than expected, which points to low airflow.AirflowCheck the filter, ductwork and blower speed.Warning
274Limit switch open more than three minutesThe high limit has stayed open long enough for the control to treat it as a hard fault. This is an airflow problem until proven otherwise.AirflowReplace the filter and open every register.Critical
311Heat firing rate reduced to match available airflow (cutback mode)The furnace has dropped its firing rate because it cannot get enough airflow to fire at full rate safely. It still heats, but at reduced capacity.AirflowReplace the filter and open all registers.Info
10Unknown device on the systemThe thermostat found a device on the communication bus that it does not recognise, so it will not commission the system.Remove any device that is not part of the Comfort Sync system.Critical
11Cannot find a previously installed componentA device that was commissioned earlier has gone missing from the bus.Check the breaker and disconnect for the missing unit.Critical
12Cannot find a Comfort Sync indoor unitThe thermostat cannot see any communicating indoor unit at all, so nothing will run.Confirm 24VAC at the indoor unit control.Critical
14More than one thermostat or unit foundThe thermostat sees duplicate devices of the same type - for example two indoor units - which it cannot resolve.Disconnect the extra device.Critical
18Outdoor temperature below heat pump lockoutNormal behaviour. It is too cold outside for the heat pump, so the system is using the furnace or electric heat instead.Nothing to fix. Adjust the balance point setting if the lockout temperature is not what you want.Info
19Outdoor temperature above furnace or electric heat lockoutNormal behaviour. It is warm enough outside that the thermostat will not allow the furnace or electric heat to run.Nothing to fix. Adjust the lockout setting if needed.Info
29Indoor temperature above 99F - heating blockedThe thermostat is reading over 99F indoors and will not allow any heating until it drops below that.Compare the thermostat reading with a separate thermometer.Critical
30Indoor temperature below 40FThe thermostat is reading under 40F indoors.Check for other active alerts pointing at a heating failure.Warning
31Lost communication with a component for over three minutesThe thermostat has not heard from one of the system components for more than three minutes, so that component stops being used.Check every bus connection for tight, clean contact.Critical
32Component is resetting itselfA system component keeps restarting. Often seen during a power disturbance, but a repeating reset means a real problem.Log incoming voltage over a full cycle.Warning
34Capacity (tonnage) of indoor or outdoor unit unknownThe thermostat does not know the equipment capacity, so it cannot set airflow or staging.Enter the correct unit size code from the installation instructions or configuration guide.Critical
36Heating for 15 minutes with no heat demandThe system has been producing heat without the thermostat asking for it.Check whether the gas valve or electric heat is energised with no call.Critical
37Cooling for 15 minutes with no cool demandThe system has been cooling without the thermostat asking for it.Check the contactor for welded contacts.Critical
38Cannot turn heating on for over 45 minutesThe thermostat has been calling for heat for 45 minutes and nothing has happened.Look for other active alerts on the furnace - they will name the real fault.Critical
39Cannot turn cooling on for over 45 minutesThe thermostat has been calling for cooling for 45 minutes with no result.Check the outdoor disconnect and breaker.Critical
40Heat pump not making progress toward setpointThe heat pump could not raise the room temperature by half a degree in 30 minutes, so the system switched to the secondary heat source and may lock the heat pump out for up to 120 minutes.In mild weather, have the charge and defrost operation checked.Info
105A component has lost communication with the systemOne device dropped off the communication bus.Identify which unit is missing, then check its power and bus connections.Critical
110Component line voltage too lowIncoming line voltage at the reporting unit is below its usable range.Measure voltage at the unit while it runs.Critical
111Line power wiring reversedLine and neutral are swapped at the unit. The control detects this because it needs a proper neutral reference.Correct the wiring so line goes to the black lead and neutral to white.Critical
112Cannot find earth groundThe control has no valid earth ground reference, which it needs both for safety and for flame sensing.Confirm the equipment ground is bonded to the furnace chassis.Critical
113Line voltage too highIncoming line voltage is above the acceptable range.Measure and log supply voltage; report sustained high voltage to the utility.Critical
114Power frequency or distortion problemThe power reaching a component is distorted or off-frequency enough to upset the control.If the building is on generator or inverter power, check its output quality.Warning
11524VAC power out of rangeLow-voltage power to a component is outside the required 18-30VAC window. On damper control modules this also covers low secondary 24VAC.Measure 24VAC at the component while everything runs.Critical
117Poor earth groundingThe unit has a ground, but it is a poor one. This often shows up as intermittent flame sense problems.Clean and re-terminate the ground to bare metal on the furnace chassis.Info
120Delayed response from a componentA component is answering the thermostat, but too slowly.Check bus wiring quality and separation from line voltage runs.Warning
124Lost communication with a component for over three minutesSame condition as alert 31 - the thermostat has not heard from a component for over three minutes.Check bus connections and power at the affected unit.Critical
125Hardware problem on a component controlA control board has reported an internal hardware failure.Cycle power once; replace the control if the alert returns.Critical
126Internal communication problem on a componentA component's internal communication - between its own processor and subsystems - has failed.Reseat internal harnesses, then replace the control if it persists.Critical
130Air handler jumper missingA configuration jumper the interface module expects is not installed.Fit the jumper as shown in the installation instructions for the configuration in use.Warning
131Component control parameters corruptedThe stored configuration in a control has been corrupted.Reconfigure the unit. If it corrupts again, replace the control.Critical
132Component control software corruptedThe firmware in a control has been corrupted and it cannot run reliably.Re-flash the firmware if the tool is available, otherwise replace the control.Critical
180Outdoor temperature sensor problemThe system's outdoor temperature sensor is reading incorrectly, so balance point and defrost logic are compromised.Measure sensor resistance against the temperature chart.Critical
200Roll out limit switch openThe flame rollout switch has tripped, meaning flame or hot gas came out of the burner area. This is a serious safety trip.Do not simply reset and walk away - find the cause first.Critical
204Issue with the gas valveThe control has detected a problem with the gas valve circuit.Check for 24VAC at the valve during a heat call and measure the valve coil resistance.Critical
205Gas valve relay contact closedThe control sees the gas valve relay closed when it should be open - a safety concern.Replace the control board. Do not leave the furnace in service with a stuck gas valve relay.Critical
206Gas valve second-stage relay faultyThe second-stage gas valve relay is not working correctly, so high fire is unavailable or uncontrolled.Replace the control board.Critical
207Hot surface igniter openThe igniter circuit is open, so the furnace cannot light.Measure igniter resistance - an open reading confirms it.Critical
223Low pressure switch openThe low pressure switch is open when the control expects it closed.Inspect the vent and intake terminations for blockage.Critical
224Low pressure switch stuck closedThe low pressure switch is closed with the inducer off, which the control tests for before every cycle.Disconnect the hose and confirm the switch opens.Critical
225High pressure switch failing to closeThe high pressure switch is not closing when the inducer runs at high speed.Check vent length, elbow count and termination.Critical
226High pressure switch stuck closedThe high pressure switch is closed with the inducer off.Confirm the switch opens with the hose removed and the inducer off.Critical
227Low pressure switch open in run modeThe low pressure switch opened while the furnace was already running.Check for water in the pressure hoses and the collector box drain.Warning
228Control cannot calibrate the pressure switchThe control runs a pressure switch calibration routine and it did not complete.Verify the vent system against the installation instructions and check hoses for leaks.Warning
229Switched to high fire ignition - low fire pressure switch did not close in timeThe furnace could not prove low fire in time, so it lit on high fire instead. It still heats, but something is marginal.Check the vent and hoses. This often precedes a hard pressure switch fault.Info
240Flame current lowThe flame signal is weaker than it should be. The furnace still runs but will eventually start dropping out.Clean the flame sensor with fine steel wool.Warning
241Flame going out while heatingFlame is being established but then lost during the heating cycle.Clean the sensor and re-check microamps.Critical
270WatchGuard - igniter cannot turn on the flameThe furnace has gone into WatchGuard mode because ignition kept failing.Check igniter resistance and gas pressure.Critical
271WatchGuard - low pressure switch openWatchGuard mode entered because the low pressure switch would not stay closed.Inspect the vent and hoses, then verify inducer performance.Critical
272Low pressure switch open during run modeThe low pressure switch opened during an active heating cycle.Drain any water from the pressure hoses and collector box.Critical
273Flame going off during a heating cycleFlame is dropping out mid-cycle.Clean the sensor, check microamps and measure gas pressure while running.Critical
275Flame out of sequenceFlame was detected at a point in the cycle when there should not be any.Shut off the gas and see whether the alert clears - if it does, the valve is passing gas.Critical
276Cannot calibrate, or high pressure switch opened or failed to close in run modeThe pressure switch calibration or high pressure switch behaviour is out of specification during operation.Verify vent length and terminations against the installation instructions.Critical
290Problem with the ignition circuitThe control has detected a fault in the ignition circuit itself.Measure igniter resistance and check for line voltage at the igniter during the trial for ignition.Critical
294Over current in the inducer motorThe combustion air inducer is drawing more current than allowed.Check the inducer bearings and wheel for drag or debris.Critical
310Discharge air temperature sensor issueThe supply air temperature sensor is not reading correctly.Check sensor resistance against the chart and inspect the connector.Warning
313Indoor and outdoor capacities do not matchThe indoor and outdoor unit sizes are not a matched pair. The variable speed motor has pre-set speed and torque limiters, so operating outside the design match can limit performance.Verify both unit size codes are entered correctly.Info
344Relay Y1 failureThe Y1 relay on the furnace control has failed.Replace the control board.Critical
345O relay failedThe reversing valve (O) relay did not operate - either the contacts did not close or the coil did not energise.Replace the control board.Critical
346Heat pump configuration link not cutThe air handler control still has its configuration link intact, but the installation is a heat pump and requires it cut.Cut the configuration link as directed in the air handler installation instructions.Critical
347Y1 relay failedThe first-stage cooling relay did not operate correctly.Replace the control board.Critical
348Y2 relay failedThe second-stage cooling relay did not operate correctly.Replace the control board.Critical
349O to R link needs to be restoredA configuration link on the furnace control has been cut or removed when it should be in place.Restore the O to R link per the installation instructions.Critical
350Electric heat not configured or misconfiguredThe air handler's electric heat configuration does not match what is installed.Configure electric heat to match the installed heater kit.Critical
351First stage electric heat issueStage 1 of the electric heat is not working.Check element continuity and the heater package fuses.Critical
352Second stage electric heat issueStage 2 of the electric heat is not working.Check element continuity, fuses and relay operation for that stage.Critical
353Third stage electric heat issueStage 3 of the electric heat is not working.Check element continuity, fuses and relay operation for that stage.Critical
354Fourth stage electric heat issueStage 4 of the electric heat is not working.Check element continuity, fuses and relay operation for that stage.Critical
355Fifth stage electric heat issueStage 5 of the electric heat is not working.Check element continuity, fuses and relay operation for that stage.Critical
370No 24VAC on the DS terminal for two minutes or moreThe furnace control is not seeing the expected 24VAC signal on its DS terminal.Check the DS terminal wiring against the diagram for the configuration in use.Critical
380Interlock relay failureThe interlock relay in the interface module did not operate (IFC or AHC mode only).Replace the equipment interface module.Warning
381Interlock relay stuckThe interlock relay is stuck in position (IFC or AHC mode only).Replace the equipment interface module.Warning
382Relay W1 failureThe W1 heating relay in the interface module has failed (IFC and AHC modes only).Replace the equipment interface module.Warning
400Compressor internal overload trippedThe compressor's built-in overload has opened, usually from overheating or excessive current.Let the compressor cool, then check for continuity across its windings.Critical
401Compressor ran over 18 hours continuously, or low refrigerant pressureThe compressor could not satisfy the thermostat in 18 hours of continuous running, or system pressure is low.Leak-check and verify charge.Warning
402Discharge or suction pressure out of limits, or compressor overloadedOperating pressures are outside the allowed window.Take full pressures and temperatures, check charge and clean both coils.Critical
403Compressor ran less than three minutes to satisfy demandThe compressor short-cycled. Repeated short cycling shortens compressor life.Check the thermostat cycle rate and location.Warning
404Compressor rotor lockedThe compressor is drawing locked-rotor current and will not turn.Test the run and start capacitors and any potential relay.Critical
405Compressor circuit openThere is an open circuit in the compressor path.Let the compressor cool and re-test for continuity.Critical
406Insufficient current through the START current transformerThe control is not seeing the expected current in the compressor start winding.Test the start capacitor and relay, then the compressor start winding.Critical
407Insufficient current through the RUN current transformerThe control is not seeing the expected current in the compressor run winding.Measure the run capacitor and check the compressor run winding.Critical
408Compressor running continuouslyThe compressor is not stopping when it should.Check the contactor for welded contacts and verify the control de-energises it.Critical
409Secondary voltage below 18VACLow-voltage supply to a component has fallen under 18VAC.Measure 24VAC under full load and total up the accessory VA.Warning
410Low pressure below required limitSystem low-side pressure is under the allowed limit.Leak-check the system.Warning
411Low pressure switch opened five times in one demandRepeated low-pressure trips within a single call have locked the unit out.Leak-check, then verify indoor airflow and check the coil for ice.Critical
412High pressure above required limitSystem high-side pressure is above the allowed limit.Clean the condenser coil.Warning
413High pressure switch opened five times in one demandRepeated high-pressure trips within a single call have locked the unit out.Clean the coil and confirm the outdoor fan motor is running properly - a failing condenser fan motor is the most common cause of repeat high pressure trips.Critical
414Discharge line temperature above 279FCompressor discharge temperature has exceeded its safe limit.Check charge and superheat first.Critical
415Discharge line temperature consistently above 279FDischarge temperature has stayed above the limit, so the unit locks out.Correct the cause of the repeated 414 events before resetting.Critical
416Outdoor coil sensor open, shorted or out of rangeThe outdoor coil temperature sensor is not usable, which affects defrost control.Measure sensor resistance against the chart.Critical
417Discharge line sensor open, shorted or out of rangeThe discharge line temperature sensor is not usable.Re-clamp or replace the sensor and check its resistance.Warning
418Faulty W output circuitThe auxiliary heat (W) output circuit is faulty.Check W wiring and the relay operation.Warning
419W output reported more than five errorsRepeated W output faults have escalated to a lockout.Correct the wiring fault or replace the module.Critical
420Defrost cycle took more than 20 minutesThe heat pump could not complete a defrost cycle in the allowed time.Check charge and reversing valve operation.Critical
421W output terminal on the outdoor unit miswiredThe W terminal at the outdoor unit is not wired as the system expects.Re-wire the W terminal per the installation instructions.Critical
422Compressor top cap switch exceeding thermal limitThe switch on the compressor top cap is seeing temperatures over its limit.Check charge and superheat, then clean the coil.Warning
423Inverter has detected a circuit issueThe inverter drive has flagged an internal circuit problem.Inspect for moisture, then replace the inverter if the fault repeats.Warning
424Liquid line temperature sensor malfunctionThe liquid line sensor is not reading correctly.Re-clamp or replace the sensor.Warning
425Minimum compressor speed raised for oil returnNormal protective behaviour. The control raised minimum compressor speed to make sure oil returns to the compressor in low ambient conditions.No action needed.Info
426Excessive inverter alarmsThe inverter has raised too many alarms and the unit has locked out.Review the stored fault history to find which inverter alarm repeated, then address that.Critical
427Inverter detected a DC peak faultThe inverter saw a DC current peak beyond its limit.Check compressor winding resistance and insulation before replacing the inverter.Warning
428Inverter detected high main input currentInput current to the inverter is too high.Check charge and head pressure, then compressor amp draw.Critical
429Inverter detected DC link low voltageThe inverter's DC bus voltage dropped too low.Measure supply voltage under load and torque all connections.Warning
430Compressor start-up failureThe compressor failed to start. The control will time out and retry the demand.Measure supply voltage during the start attempt.Warning
431Inverter detected PFC circuit over-currentThe inverter's power factor correction circuit saw excessive current.Log supply voltage; replace the inverter if the fault repeats with clean power.Warning
432Inverter detected DC link high voltageThe inverter's DC bus voltage went too high.Measure and log supply voltage before replacing the inverter.Warning
433Compressor phase current too highOne or more compressor phases is drawing too much current.Check charge, head pressure and compressor winding balance.Warning
434Outdoor control lost communications with the inverter for over three minutesThe outdoor control cannot reach the inverter. If this repeats within an hour the system locks out.Reseat and inspect the inverter harness and check for corrosion.Warning
435Inverter internal errorThe inverter has reported an internal failure.Replace the inverter if the error repeats after a power cycle.Warning
436Inverter heat sink temperature exceeded limitThe inverter's heat sink is running too hot.Clean the heat sink and confirm airflow across it.Warning
437Heat sink temperature sensor faultThe heat sink sensor is reading below 4F or above 264F after 10 minutes of operation, which cannot be right.Confirm good contact between the heat sink and the inverter control board, then replace the sensor if needed.Warning
438Inverter detected PFC circuit over-currentThe power factor correction circuit in the inverter saw excessive current.Log supply voltage quality before replacing the inverter.Warning
439Compressor slowdown due to high input currentProtective behaviour - the compressor speed was reduced because input current was climbing too high.Clean the coil and check charge to remove the underlying load.Info
440Compressor slowdown due to high heat sink temperatureProtective behaviour - compressor speed was reduced because the inverter heat sink got too hot.Clean the heat sink and confirm airflow across the inverter.Info
441Compressor slowdown due to high compressor currentProtective behaviour - compressor speed was reduced because compressor current was too high.Check charge and head pressure.Info
442Top cap switch opened five times in one hour - unit locked outThe compressor top cap thermal switch has tripped repeatedly, locking the outdoor unit out.Fix the cause of the repeated 422 events - usually charge or a restriction - before resetting.Critical
443Incorrect unit size code selectedThe outdoor unit's size code does not match the equipment.Enter the correct unit size code from the installation instructions.Critical
530Low damper 24VAC voltageThe damper control module's 24VAC supply is too low to drive the dampers reliably.Measure 24VAC at the module while dampers drive.Warning
532Zoning pressure switch opened (high pressure)Duct static pressure got high enough to open the zoning pressure switch. The system reverts to non-zone mode with all dampers open.Verify the bypass damper is present and adjusted correctly.Warning
542Zone 1 temperature sensor problemThe zone 1 temperature sensor is not reading correctly.Check sensor resistance and wiring.Warning
543Zone 2 temperature sensor problemThe zone 2 temperature sensor is not reading correctly.Check sensor resistance and wiring.Warning
544Zone 3 temperature sensor problemThe zone 3 temperature sensor is not reading correctly.Check sensor resistance and wiring.Warning
545Zone 4 temperature sensor problemThe zone 4 temperature sensor is not reading correctly.Check sensor resistance and wiring.Warning
594Pre-coil discharge air temperature sensor problemThe pre-coil discharge air sensor is faulty (dual fuel mode only). The alert escalates from moderate to critical after ten minutes.Check sensor resistance and connector condition.Warning
600Compressor cycled off on utility load sheddingThe utility signalled a demand response event and the compressor was shut off. Normal behaviour.No action needed. The compressor restarts when the event ends.Info
601Outdoor unit cycled off on low temperature protectionIt is too cold outside for the outdoor unit to run, so it has been shut off to protect itself.No action needed. Confirm the backup heat source is working.Info
602Low ambient conditions prevent use of the outdoor unitOutdoor temperature is below the unit's operating range.No action needed. Verify auxiliary heat is carrying the load.Info
700Thermostat temperature sensor not working properlyThe temperature sensor inside the thermostat is faulty.Compare the reading with a separate thermometer, then replace the thermostat if it is clearly wrong.Warning
701Indoor temperature above the programmed limitThe thermostat is reading an indoor temperature above the high limit it was set to alert at.Check for other active alerts, then review the alert threshold setting.Warning
702Indoor temperature below the programmed limitThe thermostat is reading an indoor temperature below the low limit it was set to alert at.Check for other active alerts, then review the alert threshold setting.Warning
703Thermostat humidity sensor not working properlyThe humidity sensor inside the thermostat is faulty, so humidity control is unreliable.Compare with a separate hygrometer, then replace the thermostat if needed.Warning
704Indoor humidity above the programmed limitIndoor humidity is above the alert threshold.Review dehumidification settings and run times.Warning
705Indoor humidity below the programmed limitIndoor humidity is below the alert threshold.Check humidifier operation and configuration.Warning

Replacement blower motors:Lennox blower motors

Carrier Infinity & Bryant Evolution system codes

Infinity and Evolution systems are communicating: the furnace or fan coil, the outdoor unit and the wall control share one data line, and the wall control shows the fault number with a short description. The same number can mean different things on the indoor unit, the outdoor unit and the zoning control, so check which component the alert names. Codes 41, 44 and 15 are the blower. 130 codes.

CodeWhat it meansCheck firstLevel
15Blower lockoutThe control has locked out because the indoor blower would not run correctly. On a variable-speed furnace this almost always points at the blower motor, its module, or the wiring to it.Blower motorKill power, then spin the blower wheel by hand - it should turn freely with no bearing noise or play.Critical
41Blower motor faultThe indoor blower motor has reported a fault to the control, or the control cannot get it to run correctly. This is the most common motor-related code on Carrier and Bryant communicating equipment.Blower motorKill power, then spin the wheel by hand - it must turn freely and quietly.Critical
44Cannot communicate with blowerThe fan coil control cannot establish serial communication with the variable-speed blower motor at all. It is not just running badly - the control cannot see it.Blower motorConfirm line voltage at the motor's 5-pin power connector.Critical
13Limit switch lockoutThe furnace tripped its high-limit or flame rollout switch too many times and has locked itself out of heating. It normally tries again automatically after about three hours.AirflowReplace the air filter and open all supply registers.Critical
33Limit fault / lost inverter communicationsOn a furnace the high-limit switch has opened, which is nearly always an airflow problem. If it stays open more than three minutes the code escalates to a 13 lockout. On 18VS/19VS equipment this code instead means the outdoor control lost the inverter.AirflowReplace the filter and check for closed dampers or crushed flex duct.Warning
161Excess static pressure stage downThe system reduced its capacity because duct static pressure is too high for the blower to deliver the requested airflow.AirflowReplace the filter and open all registers first.Warning
194Possible frozen coilThe wall control believes the indoor coil has frozen. Cooling is stopped to let it thaw.AirflowTurn the system to fan-only and let the coil thaw completely.Critical
210Excessive static pressure encounteredThe blower could not deliver requested airflow against the duct static pressure it measured.AirflowReplace the filter, open all registers and measure total external static pressure.Warning
12Blower on after power-upNot a failure. The furnace found a heat call already active when power came back on, so it ran the blower for about 90 seconds to clear heat out of the exchanger.Nothing to do - the code clears itself. If it keeps appearing, look for intermittent power or a loose 115V connection.Info
14Ignition lockoutThe furnace tried to light four times without proving flame and has stopped trying. It usually resets itself after about three hours.Confirm the manual gas valve is open.Critical
16Communication error / communication lossTwo pieces of the communicating system have stopped talking to each other over the ABCD bus. The equipment usually falls back to a limited or non-communicating mode.Check the A, B, C and D terminals at every unit and at the wall control for tight, clean connections.Critical
21Gas heating lockoutThe control has shut gas heating down and will not reset on its own - power has to be cycled. It normally means the control saw the gas valve energised when it should not have been.Check the gas valve wiring against the diagram.Critical
22Flame sense error / abnormal flame-proving signalThe control is sensing flame when the gas valve is supposed to be closed. The inducer keeps running until the condition clears.Shut the gas off and see whether the code clears - if it does, the valve is passing gas.Warning
23Pressure switch did not open (LPS or HPS closed)Before starting a heat cycle the control checks that the pressure switch is open. This code means it was already closed with the inducer off, which is a safety concern.Disconnect the tubing and confirm the switch opens.Warning
2424VAC fuse openThe 3-amp fuse on the control board has blown, so there is no low-voltage power. Something in the 24V wiring is shorted.Disconnect the thermostat wires and fit a new fuse - if it holds, the short is outside the furnace.Critical
25Invalid model / model plug faultThe board cannot read a valid model plug or size code, so it does not know what equipment it is controlling and will not run.Confirm the model plug is fully seated.Critical
26Invalid heater sizeThe fan coil cannot read a valid electric heater size code, so it will not allow electric heat to run.Check the heater size plug against the installed heater kit.Critical
27Invalid AC / HP sizeThe fan coil does not have a valid outdoor unit size configured, so it cannot set the right airflow.Verify the size plug matches the outdoor unit actually installed.Critical
31High pressure switch openOn a furnace this is the high-heat pressure switch failing to close or reopening. On outdoor equipment it is a refrigerant high-pressure trip.Furnace: check the vent for blockage, correct length and elbow count, and confirm inducer speed.Warning
32Low pressure switch openThe low-heat pressure switch - or on outdoor equipment the refrigerant low-pressure switch - is open when it should be closed. If it stays open five minutes the inducer shuts down for 15 minutes before retrying.Inspect intake and exhaust terminations for snow, nests or debris.Warning
34Ignition fault / ignition proving failureThe burner failed to light or lost flame on this attempt. The control retries up to three more times before locking out with code 14.Clean the flame sensor and verify at least 0.5 microamps DC (4-6 typical on high heat).Warning
35Modulating gas valve communications faultThe control cannot talk to the modulating gas valve, so it cannot set the firing rate.Reseat and inspect the gas valve harness.Warning
36Control fault - heater may be offThe fan coil control has detected an internal problem that may prevent electric heat from running.Confirm electric heat actually energises on a W call; replace the control if it does not.Warning
37Control fault - heater stuck onThe fan coil control believes an electric heat relay is stuck closed, which can allow heat with no call for it.Check for heater amp draw with no heat call. If heat is on without a call, replace the control board and do not leave the unit energised.Critical
42Inducer faultThe draft inducer is not running at the speed the control expects.Check the inducer for free rotation and unusual noise.Warning
43LPS open, HPS closedThe low pressure switch is open while the high pressure switch is closed - an impossible combination in normal operation, so the control flags it.Confirm each hose goes to the correct switch port.Warning
45Control faultThe control board has detected an internal hardware or software failure.Cycle power once. If the code returns, replace the control board and transfer the model plug.Critical
46Brownout event on 230VIncoming line voltage dropped below the usable range. The unit stops to protect the compressor and inverter.Measure voltage at the unit while it starts.Warning
47No 230V to unitThe control has 24V but sees no high voltage at the outdoor unit.Check the breaker and pull-out fuses.Critical
48Lost inverter communicationsThe outdoor control cannot talk to the compressor inverter drive.Reseat the inverter communication harness and check for corrosion.Critical
49230VAC dropout / compressor over currentEither the supply voltage dropped out and reset, or the compressor drew more current than allowed.Log incoming voltage over a full cycle.Warning
53Outdoor air temperature sensor faultThe outdoor air temperature thermistor is reading out of range, open or shorted. The system loses outdoor-temperature-based staging and defrost logic.Measure the thermistor resistance and compare with the temperature/resistance chart.Warning
54Outdoor suction temperature sensor faultThe suction line temperature sensor is out of range.Check the sensor is tight against a clean section of suction line and insulated.Warning
55Coil temperature sensor faultThe outdoor coil temperature sensor is out of range. Defrost control depends on this sensor.Verify sensor resistance and connector condition.Warning
56Temperature sensor out of rangeOne of the outdoor thermistors is reading a value the control considers impossible.Check both the outdoor air and outdoor coil sensors and their connectors.Warning
57Suction pressure sensor fault / freeze sensor faultThe suction pressure transducer is reading out of range - or on a geothermal unit, the freeze protection sensor has faulted.Compare the transducer reading with gauges before replacing it.Warning
58Suction thermistor range faultThe suction thermistor is outside its valid range.Re-clamp or replace the sensor.Warning
59Compressor scroll / discharge temperature out of rangeThe compressor discharge or scroll temperature has gone above the safe operating window.Check charge and superheat first - low charge is the usual cause.Warning
61Device out of range / fan inverter faultOn a System Access Module this means a wireless device is out of range. On 18VS/19VS equipment it is an outdoor fan inverter fault.Relocate the wireless device or add a repeater.Warning
62Loss of device communications / compressor no startThe SAM has lost a registered device, or on Greenspeed the compressor failed to start.Re-register the device on the SAM.Warning
63Device not registered / fan inverter over currentA device was found but never registered with the SAM, or the outdoor fan inverter is drawing too much current.Complete device registration.Warning
64Aux sensor alertAn auxiliary sensor connected to the SAM has gone into alert.Check the auxiliary sensor and its wiring.Info
65Security violated / DC volts low speed limitingA SAM security input was triggered, or the inverter is limiting compressor speed because DC bus voltage is low.Check the security input device.Info
66Outdoor fan dropped outThe outdoor fan stopped while the unit was running.Check the outdoor fan motor for free rotation, correct amp draw and thermal trip.Warning
67Stator heater faultThe compressor stator (crankcase) heating function has faulted.Check compressor winding resistance and inverter output.Warning
68Compressor sump heating active / stage 2 warm-up delayNormal protective behaviour - the unit is warming the compressor sump or holding a warm-up delay before second stage.No action needed. Expect this in cold weather or after a long off cycle.Info
69Inverter fault / compressor internal faultThe inverter drive or the compressor itself has reported an internal failure.Megger the compressor and check winding resistance before replacing the inverter.Critical
71Thermal cutout in low stage / compressor over temperatureThe compressor tripped its internal thermal protector while running in low stage.Check charge, superheat and coil cleanliness.Warning
72Thermal cutout in high stage / suction over temperatureThe compressor tripped its thermal protector in high stage, or suction temperature went above the allowed limit.Check charge and superheat, then clean the coil.Warning
73Contactor shortedThe control sees the compressor contactor closed when it has not called for it - the contacts are welded.Replace the contactor. Do not leave the unit energised with a welded contactor.Critical
74No 230V to compressor / discharge temp lockoutHigh voltage is present at the unit but not reaching the compressor, or the unit has locked out on repeated high discharge temperature.Check for voltage on both sides of the contactor with the coil energised.Critical
75Low speed no start / inverter temp out of rangeThe compressor did not start in low stage, or the inverter is running hotter than allowed.Check the start capacitor and relay where fitted.Warning
76Low stage repeat no start / fan inverter lockoutThe compressor repeatedly failed to start in low stage, or the outdoor fan inverter has locked out.Confirm compressor winding resistance and start component condition.Critical
77High speed no start / inverter over currentThe compressor would not start in high stage, or the inverter tripped on over current.Check charge and head pressure, then compressor amp draw.Warning
78High stage repeat no startRepeated failures to start in high stage have locked the unit out.Test start capacitor and relay, then the compressor itself.Critical
79Run capacitor failed / compressor no-pumpThe compressor run capacitor has failed, or on Greenspeed the compressor is turning without pumping.Measure the run capacitor in microfarads against its rating.Critical
80Low pressure switch openThe refrigerant low pressure switch has opened.Leak-check and weigh in the correct charge.Warning
81Thermal lockout in low stage (4 hours)Repeated low-stage thermal cutouts have locked the compressor out for four hours.Fix the underlying cause of the repeated code 71 trips before resetting.Critical
82Thermal lockout in high stage (4 hours)Repeated high-stage thermal or suction over-temperature trips have locked the unit out for four hours.Correct the cause of the repeated code 72 events.Critical
83Low pressure lockout (4 hours)The low pressure switch has tripped repeatedly and the unit is locked out for four hours.Leak-check the system.Critical
84High pressure lockout (4 hours)Repeated high pressure trips have locked the unit out for four hours.Clean the condenser coil.Critical
85Low contactor open / condensate overflow / compressor temp lockoutMeaning depends on the equipment: a low-stage contactor that will not close, a geothermal condensate overflow, or a Greenspeed compressor temperature lockout.Check the relevant item for the equipment type - clear the drain on geothermal units.Critical
86Low contactor closed / freeze sensor lockoutThe low-stage contactor is stuck closed, or a geothermal freeze sensor has locked the unit out.Replace a welded contactor.Critical
87High contactor openThe high-stage contactor is not closing when commanded.Check for 24V at the contactor coil and coil continuity.Critical
88Compressor / inverter lockoutRepeated compressor or inverter faults have locked the unit out, or the high-stage contactor is stuck closed.Review the stored fault history to find which fault repeated, and address that.Critical
89Start capacitor / relay failedThe compressor start capacitor or its relay has failed, or the inverter locked out on over current.Test the start capacitor and relay and replace as a set.Critical
91Inverter DC output over voltageThe inverter's DC bus voltage went above its limit.Log incoming voltage; correct a supply problem before replacing the inverter.Warning
92Inverter DC output under voltageThe inverter's DC bus voltage dropped below its limit.Measure supply voltage under load and torque all connections.Warning
93230VAC under voltageIncoming line voltage is below the acceptable range.Measure at the disconnect and at the unit while running to find where the drop occurs.Warning
94230VAC over voltageIncoming line voltage is above the acceptable range.Report sustained high voltage to the utility.Warning
95High current lockout / compressor over current lockoutThe unit has locked out after repeated over-current events.Check charge, head pressure and compressor amps against spec.Critical
96DC under voltage lockoutRepeated DC bus under-voltage events have locked the inverter out.Fix the supply voltage problem first.Critical
97DC over voltage lockoutRepeated DC bus over-voltage events have locked the inverter out.Verify supply voltage before replacing the inverter.Critical
98High torque eventThe compressor is being asked for more torque than normal, usually because it is working against high pressure.Clean the outdoor coil and check charge.Warning
99High torque lockoutRepeated high torque events have locked the compressor out.Correct the cause of the repeated code 98 events.Critical
100Zoning calibration - damper stuck or miswiredDuring duct calibration the wall control found a zone damper that did not move as expected.Watch each damper drive open and closed during calibration and confirm it matches the zone being tested.Warning
101Zoning calibration - all dampers closed check failedThe all-closed step of duct calibration did not produce the expected static pressure.Verify each damper closes fully and check the static pressure sensor tubing.Warning
102Zoning calibration - total size calculation failedThe wall control could not calculate a valid total duct size during calibration.Re-check zone configuration and repeat calibration after fixing any damper faults.Warning
103Low indoor temperature alert - zone 1 allowing aux heatZone 1 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
104Low indoor temperature alert - zone 2 allowing aux heatZone 2 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
105Low indoor temperature alert - zone 3 allowing aux heatZone 3 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
106Low indoor temperature alert - zone 4 allowing aux heatZone 4 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
107Low indoor temperature alert - zone 5 allowing aux heatZone 5 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
108Low indoor temperature alert - zone 6 allowing aux heatZone 6 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
109Low indoor temperature alert - zone 7 allowing aux heatZone 7 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
110Low indoor temperature alert - zone 8 allowing aux heatZone 8 has dropped far enough below setpoint that the wall control is allowing auxiliary or emergency heat to help catch up.Normal in very cold weather. If it happens in mild weather, check the zone damper and heat pump operation.Info
128Low pressure switch openRefrigerant low pressure switch has opened (single-stage outdoor unit code set).Leak-check, then confirm indoor airflow and blower operation.Warning
129High pressure switch openRefrigerant high pressure switch has opened.Clean the coil and verify the outdoor fan motor runs at full speed.Warning
130Outdoor air temperature sensor faultThe outdoor air temperature sensor is out of range.Check sensor resistance against the chart.Warning
131Coil temperature sensor faultThe outdoor coil temperature sensor is out of range.Check sensor resistance and connector.Warning
132Temperature sensor out of rangeAn outdoor temperature sensor is reading an impossible value.Test both outdoor thermistors.Warning
133Contactor shortedThe compressor contactor contacts are welded closed.Replace the contactor.Critical
134Thermal cutout in low stageThe compressor tripped its thermal protector in low stage.Check charge and coil cleanliness.Warning
135Thermal cutout in high stageThe compressor tripped its thermal protector in high stage.Check charge and airflow.Warning
136No 240V at compressorLine voltage is present at the unit but not at the compressor.Check voltage across the contactor and compressor terminals.Critical
137Thermal lockout in low stageRepeated low-stage thermal cutouts have locked the compressor out.Correct the repeating cause.Critical
138Thermal lockout in high stageRepeated high-stage thermal cutouts have locked the compressor out.Correct the repeating cause.Critical
160Humidity sensor faultThe wall control's humidity sensor is not reading correctly, so humidity control is disabled.Replace the wall control if humidity readings are clearly wrong.Warning
162Remote sensor faultA remote temperature sensor wired to the wall control is not reading correctly.Check the sensor and its wiring.Warning
170Smart Sensor zone 1 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 1.Check the sensor's bus wiring, then swap the sensor to test.Warning
171Smart Sensor zone 2 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 2.Check the sensor's bus wiring, then swap the sensor to test.Warning
172Smart Sensor zone 3 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 3.Check the sensor's bus wiring, then swap the sensor to test.Warning
173Smart Sensor zone 4 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 4.Check the sensor's bus wiring, then swap the sensor to test.Warning
174Smart Sensor zone 5 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 5.Check the sensor's bus wiring, then swap the sensor to test.Warning
175Smart Sensor zone 6 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 6.Check the sensor's bus wiring, then swap the sensor to test.Warning
176Smart Sensor zone 7 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 7.Check the sensor's bus wiring, then swap the sensor to test.Warning
177Smart Sensor zone 8 communication faultThe wall control has lost communication with the Smart Sensor assigned to zone 8.Check the sensor's bus wiring, then swap the sensor to test.Warning
178Indoor unit communication faultThe wall control cannot communicate with the indoor unit.Check 24V at the indoor board and the ABCD connections at both ends.Critical
179Outdoor unit communication faultThe wall control cannot communicate with the outdoor unit.Confirm the outdoor disconnect is on and check the ABCD run.Critical
180Zone 1-4 communication faultThe wall control cannot communicate with the damper control module handling zones 1 to 4.Check power and bus wiring at the zone 1-4 damper control module.Critical
181Zone 5-8 communication faultThe wall control cannot communicate with the damper control module handling zones 5 to 8.Check power and bus wiring at the zone 5-8 damper control module.Critical
182NIM communication faultThe wall control cannot communicate with the Network Interface Module used for zoning.Check power and bus wiring at the NIM.Critical
186SAM communication faultThe wall control has lost communication with the System Access Module.Check the SAM's bus connection and power.Warning
187Low room temperature alertThe indoor temperature has dropped below the alert threshold set in the wall control.Check for an active heating fault - this is an alert, not a fault in itself.Info
188High room temperature alertThe indoor temperature has risen above the alert threshold.Check for an active cooling fault.Info
189High humidity alertIndoor humidity has risen above the alert threshold.Check dehumidification settings and run times.Info
190Entering water temperature sensor faultThe geothermal entering water temperature sensor is out of range.Check sensor resistance.Warning
192SAM radio test failedThe System Access Module's radio self-test did not pass.Retry the test; replace the SAM if it keeps failing.Warning
193SAM profile failedThe SAM could not load its configuration profile.Re-run SAM setup.Warning
195Utility curtailment eventThe utility has signalled a load-shedding event and the system is running at reduced capacity.Nothing to fix - normal demand response behaviour.Info
196Auxiliary input (G) shutdownAn auxiliary input configured for shutdown has been triggered.Find the device on the auxiliary input - a condensate float switch is the usual one - and clear its cause.Warning
198Auxiliary input (G) alertAn auxiliary input configured as an alert has been triggered.Check the accessory wired to the auxiliary input.Info
211Zone 1 airflow limited - stage down occurredThe system had to reduce capacity because zone 1 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
212Zone 2 airflow limited - stage down occurredThe system had to reduce capacity because zone 2 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
213Zone 3 airflow limited - stage down occurredThe system had to reduce capacity because zone 3 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
214Zone 4 airflow limited - stage down occurredThe system had to reduce capacity because zone 4 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
215Zone 5 airflow limited - stage down occurredThe system had to reduce capacity because zone 5 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
216Zone 6 airflow limited - stage down occurredThe system had to reduce capacity because zone 6 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
217Zone 7 airflow limited - stage down occurredThe system had to reduce capacity because zone 7 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning
218Zone 8 airflow limited - stage down occurredThe system had to reduce capacity because zone 8 could not accept the airflow the equipment wanted to deliver.Confirm the zone damper opens fully and the branch duct is clear.Warning

Heil, Tempstar, Comfortmaker & Arcoaire LED flash codes

Furnaces built by ICP and sold as Heil, Tempstar, Comfortmaker, Arcoaire and KeepRite flash an LED on the control board, and the count is the code. Two and three flashes are pressure switch faults, four is an open high limit and six points at the inducer motor, not the blower. 8 codes.

CodeWhat it meansCheck firstLevel
1 flashIgnition failureThe furnace attempted to light and failed.Clean the flame sensor and check the igniter.Critical
2 flashesPressure switch stuck openThe pressure switch is not closing when the inducer runs.Check the tubing and vent for blockage.Critical
3 flashesPressure switch stuck closedThe pressure switch is closed with the inducer off.Confirm the switch opens with the hose off.Critical
4 flashesHigh limit switch openThe high limit has opened, which points to restricted airflow.AirflowReplace the filter and open all registers.Critical
5 flashesRollout switch trippedThe flame rollout switch has tripped - flame or hot gas escaped the burner area. Serious safety trip.Find and correct the cause before resetting.Critical
6 flashesFaulty inducer motorThe draft inducer motor is not performing as required.Check the inducer for free rotation and unusual noise.Critical
7 flashesFaulty gas valveThe gas valve or its circuit is at fault.Check for 24VAC at the valve during a heat call and measure the coil resistance.Critical
8 flashesInternal control board failureThe control board has detected an internal failure.Cycle power once, then replace the control board if the code returns.Critical

York, Coleman & Luxaire split system codes

These letter-and-number codes appear on the indoor unit display or the central controller of York, Coleman and Luxaire ducted split and central air systems. E and F codes are unit faults, P codes are protection trips and H codes come from the central controller. York gas furnaces use LED flash codes, which are not in this list yet. 34 codes.

CodeWhat it meansCheck firstLevel
Indoor EEPROM errorThe indoor unit's stored configuration memory has failed.Replace the indoor control board.Critical
Indoor and outdoor communication malfunctionThe indoor and outdoor units cannot talk to each other.Check the interconnecting wiring end to end.Critical
Indoor fan speed malfunctionThe indoor fan is not running at the speed the control commanded, or the control cannot read its speed feedback. This is the main indoor blower motor fault code on York ducted splits.Kill power and spin the blower wheel by hand - it must turn freely.Critical
Indoor room temperature sensor errorThe return air temperature sensor (T1) is out of range.Check sensor resistance against the temperature chart.Warning
Evaporator coil temperature sensor errorThe indoor coil temperature sensor (T2) is out of range.Re-seat or replace the coil sensor.Warning
Dual indoor unit communication malfunctionOn twin installations, the two indoor units cannot communicate.Check the twin interconnect wiring and addressing.Critical
Other twin model malfunctionA twin-model specific fault other than communication.Verify both units are the same model and correctly configured as a twin pair.Warning
Refrigerant leak detection system malfunctionThe refrigerant leak detection function has flagged a problem.Leak-check the system and verify charge.Critical
Water level alarm malfunctionThe condensate water level alarm has triggered.Clear the drain line and trap.Critical
Overload protectionThe system has shut down on overload protection.Clean both coils, verify charge and check compressor amp draw.Critical
Outdoor temperature sensor errorThe outdoor ambient sensor (T4) is out of range.Check sensor resistance.Warning
Outdoor condenser pipe sensor errorThe outdoor coil pipe sensor (T3) is out of range.Re-clamp or replace the sensor.Warning
Discharge air temperature sensor errorThe compressor discharge temperature sensor (T5) is out of range.Re-seat or replace the sensor.Warning
Outdoor EEPROM errorThe outdoor unit's stored configuration memory has failed.Replace the outdoor control board.Critical
Outdoor fan speed malfunction (DC fan motor)The outdoor DC fan motor is not running at the commanded speed. Applies to inverter units with a DC condenser fan motor.Check the fan spins freely and the blade is undamaged.Critical
T2b sensor errorThe secondary evaporator coil sensor is out of range.Check sensor resistance and connector.Warning
Auto-lifting panel communication errorThe control cannot communicate with the motorised front panel.Reseat the panel harness.Warning
Auto-lifting panel malfunctionThe motorised front panel is not operating correctly.Clear any obstruction and test the panel motor.Warning
Auto-lifting panel is openThe motorised panel is in the open position.Close the panel or clear whatever is holding it open.Info
Net communication malfunctionThe central controller has lost network communication with the units.Check network wiring and unit addressing.Critical
Outdoor decreasing malfunction (host unit)The controller detected fewer outdoor units than it expects.Check power and network wiring at each outdoor unit.Warning
Outdoor adding malfunction (host unit)The controller detected more outdoor units than it expects.Check unit addressing for duplicates.Warning
Inverter module (IPM) protectionThe inverter power module has gone into protection.Check the heat sink and its thermal contact.Critical
High or low voltage protectionSupply voltage is outside the acceptable range.Measure and log supply voltage under load.Critical
Compressor top overheating protectionThe compressor top temperature has exceeded its limit.Check charge and superheat, then clean the coil.Critical
Outdoor low temperature protectionIt is too cold outside for the unit to run in this mode.No action needed - the unit resumes when conditions allow.Info
Compressor drive errorThe inverter cannot drive the compressor correctly.Measure compressor winding resistance and insulation before replacing the inverter.Critical
Mode conflictTwo indoor units are calling for conflicting modes, such as heating and cooling at once.Set all indoor units to compatible modes.Warning
Compressor low-pressure protectionSystem low-side pressure has dropped below the safe limit.Leak-check the system.Critical
Outdoor IGBT sensor errorThe IGBT (inverter switching device) temperature sensor is out of range.Check the sensor and its mounting.Warning
Compressor current 3rd stage protectionCompressor current has tripped the third and highest protection stage.Check charge, head pressure and compressor amps.Critical
Defrost protectionThe system is in defrost protection.No action needed.Info
Oil returnThe system is running an oil return cycle.No action needed.Info
Oil balanceThe system is running an oil balance cycle.No action needed.Info

Replacement blower motors:York blower motorsColeman blower motors

Ducane & Armstrong Air red LED flash codes

Ducane and Armstrong Air furnaces, built by Lennox, flash a red LED on the ignition control. Count the flashes: two is a pressure switch closed with the inducer off, three a low-fire pressure, rollout or limit switch open, and four an open high limit. 8 codes.

CodeWhat it meansCheck firstLevel
1 flashFlame present with gas valve offFlame is detected when the gas valve should be closed.Clean the flame sensor rod.Critical
2 flashesPressure switch closed with inducer offThe pressure switch is closed when the inducer is not running.Confirm the switch opens with the hose off.Critical
3 flashesLow fire pressure, rollout or limit switch openA low fire pressure, rollout or limit switch is open.Inspect the heat exchanger and vent.Critical
4 flashesHigh limit switch openThe high limit has opened - an airflow problem.AirflowReplace the filter and clean the blower wheel.Critical
6 flashesPressure switch cycle lockoutThe pressure switch has cycled too many times and the control has locked out.Clear the vent and condensate drain, then replace the switch if needed.Critical
7 flashesLockout - no ignitionThe furnace has locked out because it never lit.Clean the flame sensor and check the igniter.Critical
8 flashesLockout - too many flame dropoutsFlame kept dropping out until the control locked out.Clean or replace the flame sensor.Critical
9 flashesPolarity and phasing errorLine voltage polarity or phasing is wrong.Correct the line and neutral wiring.Critical

Replacement blower motors:Lennox-built blower motors

How to read your HVAC fault code

Where do I find the error code on my furnace or heat pump?

It depends on the equipment. Most gas furnaces flash the code on an LED on the control board, behind the blower compartment door. Some modulating furnaces, such as the Rheem R96V, show it on a small seven-segment display instead. Communicating systems (Carrier Infinity, Bryant Evolution, Lennox iComfort and Comfort Sync) show the code and a short description on the wall control. Ductless and ducted split systems usually show a letter-and-number code such as E3 or F5 on the indoor unit display.

How do I read a flashing LED code?

Count the flashes between pauses. On most brands the count is the code, so four flashes is code 4. Carrier, Bryant and Payne 58-series furnaces use two digits: short flashes are the first digit and long flashes the second, so three short and three long is code 33. Codes change between board revisions, so compare against the diagram printed inside the access panel of your unit.

What does a blinking red or green light on my furnace mean?

It depends on the brand, so the color alone is not a diagnosis. On many furnaces a green LED shows normal status, while a red or amber LED that blinks in a repeating count is a fault code: count the blinks between pauses and search that count here with your brand, for example Goodman 3 flashes or Trane 4 blinks. A light that stays solid red or flashes without a pause is a separate code on Goodman, Amana and Trane boards.

How do I clear a furnace error code?

Fix the cause first, then reset. Many controls clear a lockout on their own: Rheem R96V boards lift a soft lockout after one hour, and Carrier 58-series boards reset a limit lockout after about three hours. You can also switch the power off at the furnace service switch and back on. If the same code returns, the fault is still there. Do not keep resetting flame rollout, limit or gas valve codes: have a licensed technician check the furnace.

Why does the same code mean different things on different equipment?

Because a code only means something on the board that generated it. On Carrier Infinity equipment 41 is a blower motor fault, while on another manufacturer's board the same number can point at something unrelated. On communicating systems the same number can even differ between the indoor unit, the outdoor unit and the zoning control. That is why every result here names the brand, the equipment family and the component it applies to.

Which codes point at a bad blower motor?

Codes that name the blower directly: Carrier Infinity and Bryant Evolution 41 (blower motor fault), 44 (cannot communicate with the blower) and 15 (blower lockout); Lennox 201 (lost communication with the indoor blower motor), 202 (motor size mismatch), 292 (blower will not start) and 295 (blower overheating); Rheem and Ruud 60 and 61 (blower fault, motor can or cannot run). High limit codes, such as Carrier 13 and 33, Lennox 250 and 274, and four flashes on Goodman, Amana, Trane and Arcoaire furnaces, are airflow faults: a failing blower motor is one cause, and so are a dirty filter, a dirty blower wheel and restricted ductwork. Before you order a part, run the checks in our ECM motor testing guide or the multimeter test.

My blower motor code came back after I replaced the motor. Why?

Almost always because the restriction behind it is still there. A blower motor that trips on thermal overload or hits its torque limit is usually pushing air through a dirty filter, a dirty blower wheel, a plugged coil or undersized ductwork. Replace the filter, clean the wheel and coil, and measure total external static pressure against the blower table before you fit a new motor, otherwise the new one fails the same way. On two-piece ECM motors the control module fails far more often than the motor itself, so test it separately (ECM 2.3, 2.5, 3.0 and EON guide; for one-piece motors, the X13 guide). On Lennox and Rheem equipment the horsepower of the replacement must match the original exactly, or the control throws a size-mismatch code (Lennox 202, Rheem d6). If a motor you bought from us shows a code, see what to do when a new motor shows an error code.

Is a code the same thing as a diagnosis?

No. A fault code tells you which safety or sensor the control tripped on, not which part failed. A high limit code means the furnace got too hot: that can be a dirty filter, a closed damper, a slipping blower wheel, a failing motor or a bad limit switch. Use the code to narrow down where to look, then measure. For symptom-based checks, start with our blower motor troubleshooting guide. Anything involving gas, flame rollout, a cracked heat exchanger or line voltage belongs to a licensed technician.

My code isn't listed. What now?

Fault codes vary between manufacturers, product lines and board revisions, so no single list covers everything. Check the diagram inside your unit's access panel and the manufacturer references on this page. If you still can't place it, send us the code with the model and serial number from the rating plate and we'll look it up. Not sure what equipment you have? Decode the rating plate with our HVAC serial number lookup.

Code not listed?

Send us the code with the model and serial number from the rating plate and our tech team will look it up.